Call for Price
The SUNTEC T4 oil pump is specially designed for industrial heating applications using light or heavy oils with high capacity. It is fitted with a preheater location to render cold starting easier.
TECHNICAL DATA
General
Mounting Flange mounting
Connection threads Cylindrical according to ISO 228/1
Inlet G 3/4
Pressure outlet G 3/4
Pressure gauge port G 1/4
Vacuum Gauge port G 1/4
Shaft Ø 20 mm
Weight 7,8 kg (T2) – 8,1 kg (T3)
8,7 kg (T4) – 9,4 kg (T5)
Hydraulic data
Nozzle pressure range 40 bars max. (T2, T3, T4)
30 bars max. (T5)
Operating viscosity 2 – 75 mm²/s (cSt)
(Higher viscosity oil can be used by feeding the pump and by heating the oil to lower its viscosity under 75 cSt. For kerosene applications, contact SUNTEC).
Oil temperature 0 – 150°C in the pump
Inlet pressure light oil : 0,45 bars max. vacuum to prevent air separation from oil.
Heavy oil : 5 bars max.
Rated speed 3600 rpm max.
Torque (@ 40 rpm) 0,4 N.m
Choice of heater
Cartridge Ø 12 mm
Fitting according to EN50262
Rating 80-100 W